In February 2012, a feeder at one of the sites experienced a short circuit condition causing both A and B phases at the connected substation to experience a 50% voltage sag which activated the inverters’ LVRT capabilities. The relays on the line detected the event, and cleared the fault in approximately 7 cycles. After collecting the Schweitzer Engineering Laboratories (SEL) graphs, it was evident that the inverters successfully rode through the event and returned to normal operation upon clearance of the short circuit condition.
The following month, a total of four low-voltage events occurred at PG&E’s Shindler substation, outside of Fresno, CA. These events were caused by momentary phase to phase faults on the circuit at the substation. Scope traces from the Westside Solar Station showed close to a 50% voltage depression at the 12 kV bus for approximately 5 cycles during each of these events with the inverters between 20% and 80% of full power. Despite all of these interferences, the inverters at both sites remained online, in large part due to the LVRT capability of the utility inverters PG&E has chosen to install.
To further demonstrate these events, Figure 1 shows where the current temporarily went up for about 2 cycles at the inception of the faults. This is expected behavior as the inverters are operating at less than 50% of nameplate. When the line voltage began to drop the inverters attempted to maintain a constant output power and the AC current increased up to its limit before the LVRT features were activated.